Trane RTHD Beverage Dispenser User Manual


 
17
RLC-PRC020-EN
General Data
Minimum/Maximum Evaporator Flow Rates (Gallons/Minute )
Two Pass Three Pass Four Pass
Evaporator Nominal Nominal Nominal
Code Min Max Conn Size (In.) Min Max Conn Size (In.) Min Max Conn Size (In.)
B1 253 1104 8 168 736 6 —- —- —-
B2 288 1266 8 192 844 6 —- —- —-
C1 320 1412 8 213 941 6 —- —- —-
C2 347 1531 8 232 1022 6 —- —- —-
D1 415 1812 8 275 1206 8 —- —- —-
D2 450 1980 8 300 1320 8 —- —- —-
D3 486 2131 8 324 1417 8 —- —- —-
D4 351 1542 8 234 1028 8 —- —- —-
D5 351 1542 8 234 1028 8 —- —- —-
D6 293 1287 8 196 860 8 —- —- —-
E1 450 1980 8 300 1320 8 —- —- —-
F1 563 2478 10 376 1655 8 —- —- —-
F2 604 2667 10 404 1780 8 —- —- —-
G1 —- —- —- 505 2218 10 379 1666 8
G2 —- —- —- 550 2413 10 411 1807 8
G3 —- —- —- 622 2732 10 466 2050 8
Notes:
1. Minimum flow rates are based on water only.
2. All water connections are grooved pipe.
Minimum/Maximum Evaporator Flow Rates (Liters/Second)
Two Pass Three Pass Four Pass
Evaporator Nominal Nominal Nominal
Code Min Max Conn Size (mm) Min Max Conn Size (mm) Min Max Conn Size (mm)
B1 16 70 200 11 46 150 —- —- —-
B2 18 80 200 12 53 150 —- —- —-
C1 20 89 200 13 59 150 —- —- —-
C2 22 97 200 15 65 150 —- —- —-
D1 26 114 200 17 76 200 —- —- —-
D2 28 125 200 19 83 200 —- —- —-
D3 31 134 200 20 89 200 —- —- —-
D4 22 97 200 15 65 200 —- —- —-
D5 22 97 200 15 65 200 —- —- —-
D6 18 81 200 12 54 200 —- —- —-
E1 28 125 200 19 83 200 —- —- —-
F1 36 156 250 24 104 200 —- —- —-
F2 38 168 250 25 112 200 —- —- —-
G1 —- —- —- 32 140 250 24 105 200
G2 —- —- —- 35 152 250 26 114 200
G3 —- —- —- 39 172 250 29 129 200
Notes:
1. Minimum flow rates are based on water only.
2. All water connections are grooved pipe.
Minimum/Maximum Condenser Flow Rates
(Gallons/Minute)
Two Pass
Condenser Nominal
Code Min Max Conn Size (In.)
B1 193 850 6
B2 212 935 6
D1 193 850 6
D2 212 935 6
E1 291 1280 8
E2 316 1390 8
E3 325 1420 8
E4 245 1080 8
E5 206 910 8
F1 375 1650 8
F2 355 1560 8
F3 385 1700 8
G1 444 1960 8
G2 535 2360 8
G3 589 2600 8
Notes:
1. Minimum flow rates are based on water only.
2. All water connections are grooved pipe.
Minimum/Maximum Condenser Flow Rates
(Liters/Second)
Two Pass
Condenser Nominal
Code Min Max Conn Size (mm)
B1 12 54 150
B2 13 59 150
D1 12 54 150
D2 13 59 150
E1 18 81 200
E2 20 88 200
E3 21 90 200
E4 15 68 200
E5 13 57 200
F1 24 104 200
F2 22 98 200
F3 24 107 200
G1 28 124 200
G2 34 149 200
G3 37 164 200
Notes:
1. Minimum flow rates are based on water only.
2. All water connections are grooved pipe.
Water Flow Rates