Trane SS-PRC005 Refrigerator User Manual


 
SS-PRC005-EN10
General Data
Table GD-1 — General Data — 20-120 Ton Condensing Units
Nominal Tonnage 20 25 30 40 50 60 80 100 120
Model Number RAUC-C20 RAUC-C25 RAUC-C30 RAUC-C40 RAUC-C50 RAUC-C60 RAUC-C80 RAUC-D10 RAUC-D12
Compressor Data
Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Manifolded Sets
Circuit #1 10T + 10T 10T + 15T 15T + 15T 10T + 10T 10T + 15T 15T + 15T 10T + 15T + 15T 10T + 10T 15T + 15T
+15T +15T +15T +15T
Circuit # 2 N/A N/A N/A 10T + 10T 10T + 15T 15T + 15T 10T + 15T + 15T 10T + 10T 15T +15T
+15T +15T +15T +15T
Unit Capacity Steps (%) 100-50 100-40 100-50 100-75-50-25 100-80-60-30 100-75-50-25
No Control & *19-38-50- *20-40-55 *25-50-63
VAV Option 63-81-100 70-85-100 75-88-100
EVP Option *19-38-50 *20-40-55 *25-50-63
63-81-100 70-85-100 75-88-100
Condenser Fan Data
Quantity/Fan Dia./Type 2/26”/Prop. 3/26”/Prop. 3/26”/Prop. 4/26”/Prop. 6/26”/Prop. 6/26”/Prop. 8/26”/Prop. 12/26”/Prop. 12/26”/Prop.
Fan Drive Type Direct Direct Direct Direct Direct Direct Direct Direct Direct
No. of Motors/Hp Each 2/1.0 3/1.0 3/1.0 4/1.0 6/1.0 6/1.0 8/1.0 12/1.0 12/1.0
Nominal Total Cfm 1400 0 18300 2090 0 28200 35600 4080 0 49600 66800 760 00
Condenser Coil Data
Number of Coils/Size 1/71x71 1/71x71 1/45x71 2/65x70 2/51x96 2/66x96 4/65x70 4/51x96 4/66x96
(Inches) 1/49x71
Face Area (Sq. Ft.) 35.0 35.0 46.1 63.2 67.1 88.0 126.4 134.2 176.0
Rows/Fins Per Ft. 3/144 3/144 3/144 3/144 3/144 3/144 3/144 3/144 3/144
Condenser Storage 76 76 96 136 142 184 272 284 368
Capacity (Lbs.) (2)
Refrigerant Data (3)
No. Refrigerant Circuits1 11222 222
Refrigerant Type R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22
Refrigerant Operating 28 31 40 58 62 80 116 124 160
Charge (Lbs) (1) (4) See note 4 See note 4 See note 4 See note 4 See note 4 See note 4 See note 4 See note 4 See note 4
Minimum Outdoor Air Temperature for Mechanical Cooling
Standard Ambient 40-115 40-115 40-115 40-115 40-115 40-115 40-115 40-115 40-115
Operating Range (F)
Low Ambient Option (F)0 00000 000
Notes:
1. Operating charge is approxmate for condensing unit only, and does not include charge for low side or interconnecting lines.
2. Condenser storage capacity is given at conditions of 95°F outdoor temperature, and 95% full.
3. Refer to Refrigerant Piping under Application Considerations on Page 6.
4. Condensing units are shipped with a nitrogen holding charge only.
Table GD-2 — Evaporator Chillers — 20-120 Tons
Nominal Tonnage 20 25 30 40 50 60 80 100 120
No. Of Circuits 111222222
Volume Shell (Gal) (1) 11.7 10.7 16.3 13.8 21.0 18.5 43.1 35.0 47.9
Tube Pull (In.) (2) 73 73 74 74 96 96 95 95 95
Refrigerant Operating Charge 8 10 12 16 20 24 26.8 33.4 40.4
Notes:
1. Shell volume is for waterside only.
2. Tube pull given is length of the evaporator.
3. Operating charge is approximate and for the evaporator chiller only.
Table GD-3 — EER Data — Condensing Unit Only (1)
Net Total Unit Condenser Fan
Nominal Model Capacity Compressor KW Control Condensing Unit
Tonnage Number (MBH) KW Each/Total KW Total KW EER IPLV
20 RAUC-C20 239 19.8 0.9/1.8 0.25 21.9 10.9 15.5
25 RAUC-C25 314 25.3 0.9/2.7 0.25 28.3 11.1 15.2
30 RAUC-C30 376 30.4 0.9/2.7 0.25 33.3 11.3 16.2
40 RAUC-C40 507 40.3 0.9/3.6 0.40 44.3 11.5 16.4
50 RAUC-C50 626 51.2 0.9/5.4 0.40 57.0 11.0 15.7
60 RAUC-C60 748 61.2 0.9/5.4 0.40 67.0 11.2 16.2
80 RAUC-C80 1045 87.9 0.9/7.2 0.50 95.6 10.9 16.1
100 RAUC-D10 1300 110.9 0.9/10.8 0.50 122.1 10.7 15.3
120 RAUC-D12 1560 131.5 0.9/10.8 0.50 142.6 10.9 16.2
Notes:
1. Condensing unit only ratings are in accordance with ARI standard 365. Full load ratings are at 95°F entering air temperature, and refrigerant conditions entering the
condensing unit of 45°F saturated and 60°F actual temperature. Part load ratings are at 80°F entering air temperature and refrigerant conditions entering the condensing
unit of 50°F saturated suction and 65°F actual temperature.