27SS-PRC005-EN
Electrical
Data
Table ED-1 — Condensing Units — 60 Hz
Unit Characteristics
Allowable Minimum Max. Overcurrent Recommended Dual Number
Nominal Model Voltage/Start Voltage Circuit Ampacity Protection Device Element Fuse Size Of
Tons Number Characteristics Utilization Range (1), (4) (2), (4) (3), (4) Compressors
RAUC-C20E 200/60/3XL 180-220 101 125 125 2
RAUC-C20F 230/60/3XL 207-253 101 125 125 2
20 RAUC-C204 460/60/3XL 414-506 44 60 50 2
RAUC-C205 575/60/3XL 517-633 35 45 40 2
RAUC-C25E 200/60/3XL 180-220 129 175 150 2
RAUC-C25F 230/60/3XL 207-253 129 175 150 2
25 RAUC-C254 460/60/3XL 414-506 56 80 70 2
RAUC-C255 575/60/3XL 517-633 45 60 60 2
RAUC-C30E 200/60/3XL 180-220 148 200 175 2
RAUC-C30F 230/60/3XL 207-253 148 200 175 2
30 RAUC-C304 460/60/3XL 414-506 65 90 80 2
RAUC-C305 575/60/3XL 517-633 52 70 60 2
RAUC-C40E 200/60/3XL 180-220 192 225 225 4
RAUC-C40F 230/60/3XL 207-253 192 225 225 4
40 RAUC-C404 460/60/3XL 414-506 84 100 90 4
RAUC-C405 575/60/3XL 517-633 67 80 80 4
RAUC-C50E 200/60/3XL 180-220 244 300 300 4
RAUC-C50F 230/60/3XL 207-253 244 300 300 4
50 RAUC-C504 460/60/3XL 414-506 106 125 125 4
RAUC-C505 575/60/3XL 517-633 84 100 90 4
RAUC-C60E 200/60/3XL 180-220 282 300 300 4
RAUC-C60F 230/60/3XL 207-253 282 300 300 4
60 RAUC-C604 460/60/3XL 414-506 123 125 125 4
RAUC-C605 575/60/3XL 517-633 98 110 110 4
RAUC-C80E 200/60/3XL 180-220 373 400 400 6
RAUC-C80F 230/60/3XL 207-253 373 400 400 6
80 RAUC-C804 460/60/3XL 414-506 162 175 175 6
RAUC-C805 575/60/3XL 517-633 129 150 150 6
RAUC-D10E 200/60/3XL 180-220 472 500 500 8
RAUC-D10F 230/60/3XL 207-253 472 500 500 8
100 RAUC-D104 460/60/3XL 414-506 206 225 225 8
RAUC-D105 575/60/3XL 517-633 164 175 175 8
RAUC-D12E 200/60/3XL 180-220 548 600 600 8
RAUC-D12F 230/60/3XL 207-253 548 600 600 8
120 RAUC-D124 460/60/3XL 414-506 239 250 250 8
RAUC-D125 575/60/3XL 517-633 190 200 200 8
Notes:
1. Minimum circuit ampacity (MCA) is 125 percent of the RLA of one compressor motor plus the total RLA of the remaining motors.
2. Maximum Overcurrent Protection Device permitted by NEC 440-22 is 225 percent of the RLA of one compressor motor plus the total RLA of the remaining motors.
3. Recommended dual element fuse size is 150 percent of the RLA of one compressor motor plus the total RLA of the remaining motors.
4. Local codes may take precedence.
Table ED-2— Condensing Units — 50 Hz
Unit Characteristics
Allowable Minimum Max. Overcurrent Recommended Dual Number
Nominal Model Voltage/Start Voltage Circuit Ampacity Protection Device Element Fuse Size Of
Tons Number Characteristics Utilization Range (1), (4) (2), (4) (3), (4) Compressors
20 RAUC-C20 380/415/50/3XL 360-440 42 50 50 2
25 RAUC-C25 380/415/50/3XL 360-440 55 80 70 2
30 RAUC-C30 380/415/50/3XL 360-440 64 90 80 2
40 RAUC-C40 380/415/50/3XL 360-440 80 90 90 4
50 RAUC-C50 380/415/50/3XL 360-440 104 125 125 4
60 RAUC-C60 380/415/50/3XL 360-440 122 125 125 4
80 RAUC-C80 380/415/50/3XL 360-440 159 175 175 6
100 RAUC-D10 380/415/50/3XL 360-440 201 225 225 8
120 RAUC-D12 380/415/50/3XL 360-440 237 250 250 8
Notes:
1. Minimum circuit ampacity (MCA) is 125 percent of the RLA of one compressor motor plus the total RLA of the remaining motors.
2. Maximum Overcurrent Protection Device permitted by NEC 440-22 is 225 percent of the RLA of one compressor motor plus the total RLA of the remaining motors.
3. Recommended dual element fuse size is 150 percent of the RLA of one compressor motor plus the total RLA of the remaining motors.
4. Local codes may take precedence.