Vulcan-Hart ML-710543 Oven User Manual


 
-
6 -
GAS PRESSURE REGULATOR INSTALLATION
Gas regulator pressure is preset at 5” Water Column (W.C.) for natural gas, and 10” W.C.
for propane gas. Minor adjustments may be required based on site specific gas pressure.
Install the regulator as close to the broiler on the gas supply line as possible. Make sure
that the arrow on the underside of the regulator is oriented in the direction of gas flow to
the broiler (Fig. 2) and the regulator is positioned with the vent plug and adjustment
screw upright (Fig. 3).
Fig. 2
Fig. 3
The minimum supply pressure (upstream of the regulator) should be 7-9” W.C. for natural
gas and 11-12” W.C. for propane gas. At no time should the charbroiler be connected to
supply pressure greater than ½ psig (3.45 kPa) or 14” W.C.
CASTER EQUIPPED CHARBROILERS
Charbroilers mounted on stands with casters must use a flexible connector (not supplied)
that complies with the Standard for Connectors for Movable Gas Appliances, ANSI Z21.69
• CSA 6.16 and a quick-disconnect device that complies with the Standard for Quick-
Disconnect Devices for use With Gas Fuel, ANSI-Z21.41 • CSA 6.9. In addition, adequate
means must be provided to limit movement of the broiler without depending on the
connector and the quick-disconnect device or its associated piping to limit broiler
movement. Attach the restraining device at the rear of the charbroiler. If disconnection of
the restraint is necessary, turn off the gas supply before disconnection. Reconnect the
restraint prior to turning the gas supply on and return the charbroiler to its installation
position.
Note: If the Charbroiler is installed on casters and is moved for any reason, it is
recommended that it be re-leveled (see LEVELING).
OPERATION
WARNING: THE CHARBROILER AND ITS PARTS ARE HOT. USE CARE WHEN OPERATING,
CLEANING, OR SERVICING THE CHARBROILER.
CONTROLS (Fig. 2)
OFF ON