Vulcan-Hart VB 25 ML-052313 Oven User Manual


 
– 5 –
Broilers wired for 3-phase service may be changed to 1-phase (or vice versa) by simply relocating two
of the four broiler leads on the terminal block as shown in the wiring diagram. (1-phase not available
on 480 volt models.)
All required broiler wiring diagrams are packaged separately in a clear plastic ziplock bag and shipped
with the broiler.
BROILERS WITH CONVECTION OVENS
STANDARD VOLTAGES - 208 VOLTS OR 240 VOLTS 60 Hz 1 PHASE - 480 VOLTS 60 Hz 3 PHASE ONLY
3-PHASE NOMINAL AMPS PER LINE
TOTAL LOADING 1-PHASE 3-PHASE
VOLTS KW KW PER PHASE 208V 240V 208V 240V 480V
MODEL DESCRIPTION 60 Hz CON. X-Y Y-Z X-Z X Y Z X Y Z X Y Z
VB2S Broiler w/Storage Base 208-240-480 12.0 3 6 3 58 50 25 37 37 22 32 32 16 11 16
VB21 Broiler w/Oven 208-240-480 18.7 6 6 6.7 90 78 53 50 53 45 43 45 23 21.5 23
VB22S Dbl.Broiler w/Storage 208-240-480 24.0 9 9 6 115 100 62 74 62 54 65 54 32 27 27
VB221 Dbl.Broiler w/Oven 208-240-480 30.7 12 10 8.7 148 128 86 91 78 74 79 67 40 37 34
STANDARD VOLTAGES - 208 VOLTS OR 240 VOLTS 60 Hz 1 PHASE OR 3 PHASE - 480 VOLTS 60 Hz 3 PHASE ONLY
3-PHASE NOMINAL AMPS PER LINE
TOTAL LOADING 1-PHASE 3-PHASE
VOLTS KW KW PER PHASE 208V 240V 208V 240V 480V
MODEL DESCRIPTION 60 Hz CON. X-Y Y-Z X-Z X Y Z X Y Z X Y Z
VTMB2 Single Broiler 480 12.0 3 3 6 ——————161116
VTMB2 Single Broiler 208-240 12.0 3 6 3 58 50 25 37 37 22 32 32
VTMB22 Double Broiler 480 24.0 9 6 9 ——————322727
VTMB22 Double Broiler 208-240 24.0 9 9 6 115 100 62 74 62 54 65 54
ELECTRICAL DATA CHART
”N/A” BROILERS NOT AVAILABLE IN 480V 1 PHASE
3-PHASE LOAD 3-PHASE LOAD NOMINAL AMPS PER LINE WIRE
TOTAL
KW PER PHASE KW PER PHASE 3 PHASE 1 PHASE
KW
208 & 240V 480V 208V 240V 480V 208V 240V 480V
MODEL CONN. X-Y Y-Z X-Z X-Y Y-Z X-Z X Y Z X Y Z X Y Z XYZ XYZ XYZ
VB21C 19.0 4.2 7.2 7.6 7.2 7.2 4.6 65 53 54 43 41 53 21 26 21 91 79 40
VB221C 31.0 10.2 10.2 10.6 7.2 13.2 10.6 87 85 87 75 74 75 32 337 43 149 129 N/A