ENGLISH
11.2. Control box and connecting posi-
tion of wiring
1 Outdoor unit
1. Remove the total of six screws at the top and bottom, and remove
the service panel by pulling it forward. (See the figure below.)
A Service panel
2. Remove the two screws on the left and right-hand of the base of the
control box and pull the overall cover downwards to detach it. (A dia-
gram with the control box cover removed is shown below.)
A INV board
B MAIN board
C Ten position
D One position
E Address switch
F FANCON board
G Power source
H Shield screw
I Transmission line
J RELAY board
K Shield terminal (S)
A
3. Connect indoor and outdoor units through the terminal block for trans-
mission lines (TB3). Outdoor units and connections to central control
systems go through the terminal block for centralized control (TB7).
When making an indoor/outdoor connection with shielded wiring, con-
nect the shield ground to the shield screw. When making a central
control system connection with shielded wiring, use the terminal block
for centralized control (TB7).
When the CN41 power supply connector of an outdoor unit has been
replaced with a CN40, the shield terminal (S) for centralized control
(TB7) should also be connected to the shield screw.
2 How to use the conduit mounting plate
(1) Conduit mounting plates (ø46, ø53, ø62) are being provided.
Select conduit mounting plate based on the outside diameter of con-
duit to be used and mount it as shown in the figure.
(2) Fix power source wiring to control box by using buffer bushing for
tensile force (PG connection or the like).
To prevent external tensile force from applying to the wiring connection
section of power source terminal block, use buffer bushing like PG
connection or the like.
knockout hole
T
e
n
s
i
l
e
f
o
r
c
e
A
D
A
F
G
E
B
C
B
A ø46 mounting hole
B ø53 mounting hole
C ø62 knockout hole
D For the connection of conduit at bottom
E ø62 mounting hole
F For the connection of conduit at front
G The front of outdoor unit
3 How to use the wire mounting plate
(1) When the power source and transmission lines are wired through
the knock-out hole of the left wiring, it is necessary to attach the
mounting plate onto the base of the front of the control box with two
screws.
In this case, please use the top clamp to fasten the transmission line
and the lower installation hole to fasten the power supply line.
If it does not match with the outer diameter of the power line conduit,
mount the power line conduit mounting plate (ø46) as shown in the fig-
ure below.
Also, please fasten it so that no tension is brought to bear on the power
line, as shown above.
Wire mounting plate
Ø46 mounting hole
Ø53 mounting hole
Control Box
Front side
Transmission
wire
Source wire
L1 L2 L3
TB1
TB7TB3
LD1
M1 M2M1 M2 S
N
F
J
B
CD A
E
GHI
K
Control Box
ø46 mounting hole
Transmission
wire
Source wire
Wire mounting plate
ø53 mounting hole
Front side
Tensile force
knockout hole
To prevent external tensile force from applying to the wiring connection
section of power source terminal block, use buffer bushing like PG
connection or the like.