E6581738
- 10 -
3.2. STW Control Word Data
PDP003Z supports only speed control mode.
Bit Value Name Note
1
ON
“Switched on” condition
0
0
OFF Normal stop.
1
No Coast Stop
All "Coast Stop (OFF2)" commands are withdrawn
1
0
Coast Stop (OFF 2) Coast stop.
1
No Quick Stop
All "Quick Stop (OFF3)" commands are withdrawn.
2
0
Quick Stop (OFF 3) Quick Stop
1
Enable Operation
The drive then runs-up to the setpoint.
3
0
Disable Operation Normal stop.
1 Enable Ramp Generator -
4
0
Reset Ramp Generator Output of the RFG is set to 0.
1 Unfreeze Ramp Generator -
5
0
Freeze Ramp Generator Freeze the actual setpoint entered by the RFG *.
1
Enable Setpoint The value selected at the input of the RFG is switched-in.
6
0
Disable Setpoint The value selected at the input of the RFG is set to 0.
1
Fault Acknowledge Fault reset (0 -> 1)
7
0
No meaning -
1
JOG 1 ON ** VF-MB1/S15 drives with JOG 1 speed 1 (c154).
8
0
JOG 1 OFF
Jogging stop, if "JOG 1" was previously ON. Stop drive
according to VF-MB1/S15 setting parameter.
1
JOG 2 ON ** VF-MB1/S15 drives with JOG 2 speed 2 (c155).
9
0
JOG 2 OFF
Jogging stop, if "JOG 2" was previously ON. Stop drive
according to VF-MB1/S15 setting parameter.
1
Control By PLC The control word and main setpoint are activated.
10
0
No Control By PLC The control word and main setpoint are inactivated.
11 ---
Device-specification (Reserved.)
1 Net Control PDP003Z control is enabled.
12
0 Local Control PDP003Z control is disabled.
1 Net Reference PDP003Z reference is enabled.
13
0 Local Reference PDP003Z reference is disabled.
14 ---
Device-specification (Reserved.)
15 ---
Device-specification (Reserved.)
* RFG: Ramp Function Generator
** Operation is enabled, drive is in standstill and STW1 bit 4, 5, 6 = 0.