4.1. How to use
The purposes are adjustment by real time command transmission, and the monitor of an
operation state by using cyclic communication of PROFIBUS.
Example 1: Command transmitting
When you want to set "0xC400" to parameter fa06, set “1 (fa06)” to parameter
c001.
And Since 0 and 1 byte of the PZD1 supports the parameter
c001, if "0xC400" is set up
here, "0xC400" will be set as
fa06.
Example 2: State monitoring
When you want to monitor the output current, set “3 (FD03)” to parameter
c021.
The value of the parameter
fd03 specified as 0 and1 byte of the PZD1 with the
parameter
c021 is inputted.
VF-MB1
PDP003Z
"0xC400" is set as parameter fa06
PZD1 PZD2 PZD3
C4 00 ... ... ... ...
PROFIBUS Master
Parameter Value
c001 1 (FA06)
c002 ...
c003 ...
... ...
Parameter Value
c021 3 (FD03)
c022 ...
c023 ...
... ...
The value of a parameter fd03 is outputted.
VF-MB1
PDP003Z
PZD1 PZD2 PZD3
xx xx ... ... ... ...
PROFIBUS Master