Acme Kitchenettes PP-32 Ventilation Hood User Manual


 
83
PP-32
KOOLMASTER PP-32 REV.01
RH Compensation
Add Min Vent sec 30
RH set point % 65
Mist shutoff % Off
5.15.3.2 RH Compensation on Minimum Ventilation
When the humidity level reaches the RH set point + 10%, the On-Time
portion of the minimum ventilation cycle is increased by an amount
ranging from 0 to 900 seconds. Set the dipswitch #7 to ON to activate
this function.
Set the function to "18.RH Compensation" from the main menu
using the navigation buttons then press the right-arrow key. Note
that this menu only appears if the relative humidity sensor has been
enabled during the installation setup (see sec. 5.14.3).
Use the adjustment buttons to set
the time that will be added to the
minimum ventilation's On-Time
when the humidity level reaches the
Humidity Set Point + 10%
(Add
Min Vent sec)
. Note that this menu
only appears if dipswitch #7 is
turned ON.
MAX ON TIME
ON TIME
(IN MIN. VENT.)
RELATIVE
HUMIDITY (RH)
WHEN THE HUMIDITY
EXCEEDS THE RH SET
POINT, THE ON TIME
STARTS INCREASING
RH SET POINT
NORMAL ON TIME
ON TIME +
ADDED DELAY
ADDED TIME
HUMIDITY COMPENSATION ON MIN. VENTILATION