Cooling System Performance
For maximum performance of the cooling system, operating
temperatures and pressure should be checked. Superheat
should be determined at Standard ARI test conditions of 82°F
outdoor and 80°F indoor dry bulb/67°F wet bulb. If superheat
measured deviates from values found in Table 4, refrigerant
charge should be adjusted accordingly for maximum
performance.
Suction Superheat
Table 4
eziS
taehrepuSnoitcuS
snoitidnoCIRA@
BWDI°76/BDDI°08-DO°28
22R A014
4251
03 °02 °51
6021
24 °02 °21
06,8001