Beckett SL7175 Oven User Manual


 
23
2. Clean nozzle assembly and all air handling parts.
3. Check spacing and condition of ignition electrodes. Clean and replace as required.
4. Nozzles should be inspected every year for plugged orifices. If it is necessary to replace the nozzle,
use only the specified nozzle to be sure that the replacement meets spray specifications for the boiler
burner combination.
5. Consult oil burner manufacturer’s instructions for additional maintenance requirements.
Vent System
Chimney Vent- Inspect the chimney to ensure its cleanliness, the proper size, in good condition. Remove
any accumulation that may have occurred at the clean out door. Inspect and clean all vent piping, replacing
as necessary.
Direct Vent – Inspect and clean vent and air intake piping. Replace and reseal joints as required. Inspect
vent hood air inlet and discharge for obstruction.
Domestic Hot Water Storage Tank
1. Sizing of the hot water tank must be matched with the hot water usage.
2. Piping must be in accordance with the appropriate codes and the Solaia manual.
3. Follow the installation instructions of the hot water domestic tank you have chosen to install with the
Solaia boiler.
Danger… Water temperature exceeding 125 F will cause severe burns instantly or death by scalding.
An automatic mixing valve must be installed on the outlet of the domestic waterside of the tank.
Installation must comply with the valve manufacture’s recommendations, and instructions.
Pipe in accordance with the installation manual.
Due to varying water conditions, an adjustable flow restrictor may be required in the coldwater
inlet of the tank.