GASCONNECTION
Allgasconnectionsmustcomplywithnational
andlocalcodes.Thegassupplyline(service)
mustbethesamesizeorgreaterthantheinlet
lineoftheappliance.Thisrangeusesa1/2"NPT
inlet(seedrawingbelowfordetailsofgas
connection).Onallpipejointsuseappropriate
sealant
resistanttogas.
Thisrangecanbeused withNaturalor
LP/Propanegas.Therangeisshippedfromthe
factoryforusewithnaturalgas.
ForLP/propanehouseholdinstallation,the
appliancemustbeconvertedbythedealer,bya
factory‐trainedprofessionalorbyaqualified
licensedplumberorgas
servicecompany.
Gasconversionisimportantforsafeandeffective
useoftheappliance.Itistheresponsibilityofthe
dealerandtheowneroftherangetoperformthe
appropriategasconversionfollowingthe
directionsofthemanufacturer.
THEGASCONVERSIONPROCEDUREISDESCRIBED
INTHISMANUALANDINTHE
PACKAGE
CONTAININGTHECONVERSIONNOZZLES
SHIPPEDWITHEVERYRANGE.
Pleaseprovidetheservicepersonwiththis
manualbeforeworkisstartedontherange.
WARNING!
DONOTUSEANOPENFLAMEWHENCHECKING
FORLEAKS!
Leaktestingoftheapplianceshallbeconducted
accordingtothemanufacturer'sinstructions.
Beforeplacing
theovenintooperation,always
checkforleakswithsoapywatersolutionor
otheracceptablemethod.
MANUALSHUT‐OFFVALVE
THISVALVEISNOTSHIPPEDWITH THEAPPLIANC
ANDMUSTBESUPPLIEDBYTHEINSTALLER.
Themanualshut‐offvalvemustbeinstalledin
thegasservicelinebetweenthe
gashook‐upon
thewallandtheapplianceinlet,inaposition
whereitcanbereachedquicklyintheeventofan
emergency.
InMassachusetts:A'T'handletypemanualgas
valvemustbeinstalledinthegassupplylineto
thisappliance.
FLEXIBLECONNECTIONS
In case of
installation with flexible couplings
and/or quick‐disconnect fittings, the installer
must use a heavy‐duty, AGA design‐certified
commercial flexible connector of at least 1/2"
(1.3 cm) ID NPT (with suitable strain reliefs) in
compliance with ANSI Z21.41 and Z21.69
standards.
In Massachusetts: The unit must be installed
witha
36"(3‐foot)longflexiblegasconnector.
InCanada:useCAN1‐6.10‐88metalconnectors
forgasappliancesandCAN1‐6.9M79quick
disconnectdeviceforusewithgasfuel.
PRESSURETEST‐POINTSTOPPERVALVE
To avoid gas leaks, the pressure test‐point
stoppervalveandgasketsupplied
withtherange
mustbeinstalledonthegasfittingatthebackof
therangeaccordingtothediagrambelow.