4.0 INSTALLATION INSTRUCTIONS
GENERAL
Gas installation to conform to local codes or in absence of local codes to the National Fuel Gas
Code - ANSI Z223.1 - latest edition. In Canada, installation to be according to CAN/CGA- B149.1
(NAT) or CAN/CGA-B149.2 (LP) installation codes as applicable.
1. The appliance and its individual shut-off valve must be disconnected from the gas supply piping
system during any pressure testing of that system at pressures greater than ½ psig (3.45 Kpa).
2. The appliance must be isolated from the gas supply piping system by closing its individual
manual shut off valve during any pressure testing of the gas supply piping system at test
pressures equal to or less than ½ psig (3.45 Kpa).
The installer must provide electrical grounding according to local codes, or in the absence of local
codes, with the National Electrical Code, ANSI/NFPA 70 - latest edition. In Canada installation
must be according to the C.S.A. C22.2 Canadian Electrical Code.
The electrical wiring diagram is located inside the right hand console of the appliance.
If applicable, the vent line from the gas appliance pressure regulator shall be installed to the
outdoors in accordance with the local codes or, in the absence of local codes, with the National
Fuel Gas Code, ANSI Z223.1, Natural Gas Installation Code, CAN/CGA-B149.1, or the Propane
Installation Code as applicable.
WARNING
ELECTRICAL GROUNDING INSTRUCTIONS
THIS APPLIANCE IS EQUIPPED WITH A THREE-PRONG (GROUNDING) PLUG FOR YOUR
PROTECTION AGAINST SHOCK HAZARD AND SHOULD BE PLUGGED DIRECTLY INTO A
PROPERLY GROUNDED THREE-PRONG RECEPTACLE. DO NOT CUT OR REMOVE THE
GROUNDING PRONG FROM THIS PLUG. (120 VOLT UNITS ONLY).