English 12
Installation
Electrical Installation
All model ovens on the front cover are dual rated, designed to be connected to
either 208/240V AC, 60 Hz, 4 wire, single-phase power supply.
The electrical supply should be a 4-wire single-phase AC. Install a suitable conduit
box (not furnished).
Important: Local Codes may vary, installation, electrical connections and
grounding must comply with all applicable local codes.
If local codes permit grounding through the electrical supply neutral, connect both
the white neutral wire and the bare ground wire from the oven to the white neutral
electrical supply wire.
Model Circuit Required
208V, 60 Hz 240V, 60 Hz
HBN33, HBL33 25 AMP 30 AMP
HBN34, HBL34,
HBN54, HBL54
HBL85
30 AMP 30 AMP
HBN35, HBL35,
HBN56, HBL56, HBL57,
HBL8650, HBL8750
40 or 50 Amp circuit. Refer to local electrical codes
for de-rating requirements.