Bunn CDBCF APS-MV Coffeemaker User Manual


 
Page 3
#00658.0000
#00831.0000
#29710.0000 (MV models only)
THREE WARMER BREWERS
Optional Field Wiring
120 V, 17.0 A, 2050 W
1PH, 2-Wire, 60HZ
or
120/208-240 V, 13.6-15.3 A, 2640-3430 W
1PH, 3-Wire, 60HZ
#29710.0002 (MV models only)
TWO WARMER BREWERS
Optional Field Wiring
120 V, 18.0 A, 2150 W
1PH, 2-Wire, 60HZ
or
120/208-240 V, 14.4-16.2 A, 2740-3530 W
1PH, 3-Wire, 60HZ
29707 080503
Optional Field Wiring
120/208-240 V, 14.4-16.2 A, 2740-3530 W
1PH, 3-Wire, 60HZ
#29710.0003 (DV models only)
THREE WARMER BREWERS
Optional Field Wiring
120/208-240 V, 12-13.7 A, 2440-3230 W
1PH, 3-Wire, 60HZ
#29710.0004 (DV models only)
APS BREWERS
When re-wiring the machine for operation on
120/208V or 120/240V, the replacement Power
Supply Cord must be UL Listed Flexible Cord Type
SO, SJO, SJTO, HSJO or SJOW, No. 12 AWG, 4
Conductor, Rated 90° C. Attachment Plug Cap
must be UL Listed, NEMA 14-20P or L14-20P
Configuration, Rated 125/250V, 20 AMPS. The
Power Supply Cord must be at least 3 feet long
and maximum 6 feet long (measured from Strain
Relief to end of the Attachment Plug Cap.)