CMA Dishmachines CMA-180 Dishwasher User Manual


 
ii. Run your dispenser wires through the conduit to the control box.
iii. Run your probe wires to the control box.
iv. With the machine’s power “OFF”, connect your detergent and rinse dispenser
wires to the red and blue terminals of the power block supplied inside the control
box. The table that follows lists the function of each conductor of the multi-
conductor electrical cable.
Wire Colors Circuit Voltage Function
Gray/Violet 200 VAC-249 VAC 50/60 Hz Main AC Power
Brown 200 VAC-249 VAC 50/60 Hz Main AC Power
Black
No Connection. Insulate this wire!
This wire is LIVE!
Yellow 24 VAC-240 VAC 50/60 Hz Detergent Signal
White/Yellow 24 VAC-240 VAC 50/60 Hz Detergent Signal
Violet 24 VAC-240 VAC 50/60 Hz Rinse Signal
White/Violet 24 VAC-240 VAC 50/60 Hz Rinse Signal
The individual conductors need to be connected as shown on the wire
diagram below. Probe wires are to be striped, crimped on barrel male and
female connectors provided, and connected to the pre-wired violet wires in
the control box.
MODEL CMA-180 INSTALLATION & OPERATION Rev. 2.04 Page