Safe Chill™ Blast Chillers Service & Installation Manual
For customer service, call (800) 733-8829, (800) 733-8821, Fax (989) 773-3210, www.deleld.com
4
Defrost Mode: After chilling/freezing the unit will go into a
defrost mode for 15 minutes or until the coil reaches a
temperature of 70˚(DF1). During the freezer preservation mode
the defrost heater will operate for 15 minutes (DF2) or until the
coil reaches a temperature of 70˚F(DF1) every 6 hours (DF3).
Tandem Mode (DBC-10 only): In this mode, both the upper
and lower compartments will start at the same time running in
the same mode of operation (soft, hard, or freezer mode). Once
operating the compartments cycle independently. For example,
if the bottom compartment pulls down quicker than the top it will
shut down without affecting the tops operation.
Individual Mode (DBC-10 only): This mode allows operation of
the two compartments in different modes of operation starting
them at different times. For example, the top compartment can
be loaded to run in a timed soft chill cycle, and at any time the
bottom could be loaded in a freezer mode and started.
Operating the Control
1. Start Cycle (DBC-10 will start both upper and lower
units):
• Press MODE button, display will change.
• Press MODE button until desired mode (soft, hard, freeze)
appears in left hand upper corner of display.
• Press START/STOP button, unit will start cycle.
2. Start cycle in individual mode (DBC-10 only):
• Press MODE button, display will change
• Press MODE button until “Indiv” appears in left hand upper
corner of display.
• Press ENTER button.
• Press MODE button until desired mode (soft, hard, freeze)
appears in left hand upper corner of display.
• Press START/STOP button, unit will start cycle.
3. Start cycle in timed mode (DBC-10 only will start both
upper and lower units):
• Press MODE button, display will change
• Press MODE button until “Indiv” appears in left hand upper
corner of display.
• Press TIMED button, counter will appear in right hand
upper corner of display.
• Press UP/DOWN buttons to adjust timer to desired setting.
• Press START/STOP button, unit will start cycle.
4. To stop a cycle:
• Press START/STOP button for one second.
If unit is a DBC-5 or DBC-5U cycle will shut down.
DBC-10 If only one compartment is running, cycle will shut
down. If both compartments are running, display will prompt
you to shut entire unit down by pressing START/STOP
button. To shut down the individual compartments press
the UP button for the top or the DOWN button for the
bottom.
OPERATION CONTINUED...
Safe Chill™ Control
Probe
Temp
Box
Temp
Time
Elapsed
Time
Remaining
Soft
Chill
Hard
Chill
Blast
Freeze
Dual
Mode