20
Ventilation
The room containing the cooker should
have an air supply in accordance with B.S.
5440: Part 2: Current Editions.
The following requirements for ventilation
must be met.
The cooker should not be installed in a bed
sitting room with a volume of less than
20m
3
, if it is installed in a room of volume
less 5m
3
an air vent of effective area of
110cm
2
is required; if it is installed in a room
of volume between 5m
3
and 10m
3
, an air
vent of effective area 50cm
2
is required,
while if the volume exceeds 11m
3
no air vent
is required. However, if the room has a
door, which opens directly to the outside, no
air vent is required even when the volume is
between 5m
3
and 11m
3
.
If there are other fuel burning appliances in
the same room, B.S. 5440: Part. 2: Current
Editions should be consulted to determine
the requisite air vent requirements.
Location
The cooker may be located in a kitchen, a
kitchen/diner or bed sitting room but not in a
bathroom or shower room.
For information regarding the fitting of
flexible supply pipes, the highest
temperature at the rear of this cooker which
may come into contact with the supply pipe
is 70°C above ambient.
When the appliance has been installed
there must be enough space for the hotplate
lid (when present) to open fully.
L.P.G. cookers or ovens MUST NOT
be installed below ground level, i.e. in a
basement, or aboard any boat, yacht or
other vessel.
Levelling
Fix the support with two legs by means of
washer
and nuts, delivered with the
cooker, see the figure.