Table 3 Technical data—Envirosource module, 60 Hz
Process Fluid Chiller PS018A PS024A PS036A PS048A PS060A PS096A PS120A
Model Number ENV05G ENV05G ENV10G ENV10G ENV10G ENV20G ENV20G
Circulating Fluid—Water
Flow Rate, gpm (l/s)
2.4
(.151)
3.3
(.208)
5.3
(.334)
7.9
(.498)
10.2
(.644)
16.0
(1.009)
20.0
(1.262)
Pressure Drop, feet (kPa)
13.6
(40.65)
24.9
(74.43)
11.7
(34.97)
18.6
(55.60)
30.7
(91.76)
14.2
(42.44)
23.7
(70.84)
Emergency Fluid—Water
Flow Rate, gpm (l/s)
3.6
(.227)
4.9
(.312)
8.0
(.502)
11.9
(.751)
15.3
(.965)
24.0
(1.51)
30.0
(1.89)
Pressure Drop, feet (kPa)
21
(62.77)
27.7
(82.80)
31.4
(93.85)
51.1
(152.74)
74.4
(222.38)
65.1
(194.58)
73.7
(220.29)
To prevent leaks within the Envirosource Module, the water pressure should not exceed 100 psig.
Table 4 Connection sizes (NPT male)
Model ENV05G ENV10G ENV20G
Supply from Chiller 3/4" 1" 1-1/4"
From Emergency Water Supply 1/2" 3/4" 1"
To Drain or Recirculator 1/2" 3/4" 1"
Supply to Load 3/4" 1" 1-1/4"
Table 5 Electrical data, 60 Hz
Electrical
Requirements
ENV05G ENV10G ENV20G
208/230 460 208/230 460 208/230 460
1 Ph 3 Ph 3 Ph 1 Ph 3 Ph 3 Ph 1 Ph 3 Ph 3 Ph
FLA 7.6 3.5 1.6 8.8 4.6 2.1 -- 10.6 4.8
WSA 9.9 4.4 2.0 11.0 5.8 2.6 -- 13.6 6.0
OPD 15.0 15.0 15.0 15.0 15.0 15.0 -- 15.0 15.0
*Electrical data based on standard pump selection for 40% E.G.