Emerson 3051N Waffle Iron User Manual


 
Reference Manual
00809-0100-4808, Rev CA
June 2008
Rosemount 3051N
A-4
Table A-1. Typical HART Fast Key Sequences for the Rosemount 3051 (partial listing).
Function HART Fast Key Sequence
Alarm and Saturation Levels 1, 4, 2, 7
Analog Output Alarm Type 1, 4, 3, 2, 4
Custom Meter Configuration 1, 3, 7, 2
Custom Meter Value 1, 4, 3, 4, 3
Damping 1, 3, 6
Date 1, 3, 4, 1
Descriptor 1, 3, 4, 2
Digital To Analog Trim (4–20 mA Output) 1, 2, 3, 2, 1
Disable Local Span/Zero Adjustment 1, 4, 4, 1, 7
Field Device Info 1, 4, 4, 1
Full Trim 1, 2, 3, 3
Keypad Input – Rerange 1, 2, 3, 1, 1
Local Zero and Span Control 1, 4, 4,1, 7
Loop Test 1, 2, 2
Lower Sensor Trim 1, 2, 3, 3, 2
Message 1, 3, 4, 3
Meter Options 1, 4, 3, 4
Number Of Requested Preambles 1, 4, 3, 3, 2
Range Values 1, 3, 3
Rerange 1, 2, 3, 1
Scaled D/A Trim (4–20 mA Output) 1, 2, 3, 2, 2
Self Test (Transmitter) 1, 2, 1, 1
Sensor Info 1, 4, 4, 2
Sensor Temperature 1, 1, 4
Sensor Trim Points 1, 2, 3, 3, 5
Status 1, 2, 1, 2
Tag 1, 3, 1
Transfer Function (Setting Output Type) 1, 3, 5
Transmitter Security (Write Protect) 1, 3, 4, 4
Trim Analog Output 1, 2, 3, 2
Units (Process Variable) 1, 3, 2
Upper Sensor Trim 1, 2, 3, 3, 3
Zero Trim 1, 2, 3, 3, 1
NOTE
A check () indicates the basic configuration parameters. At minimum,
these parameters should be verified as part of the configuration and
startup procedure.