6
Each Beacon II board power is supplied by a transformer in the evaporator on which
it is mounted. Do not run any 24 VAC wires between Beacon II boards on the evaporators.
Conguration
CU
M
S
S
S
M = Master Evaporator S = Slave Evaporator CU = Condensing Unit
If there are multiple evaporators on a system, the
program for each SLAVE evaporator must be changed to
identify it as a SLAVE. To do so, press the “PROGRAM
REVIEW” button repeatedly until “SLA” appears then
use the “SELECT” knob to select “YES” then press
“ENTER”. All Beacon II boards are shipped with the
factory default as a MASTER evaporator. Place all
boards in the “SERVICE” mode while you program the
setpoints to avoid errors and alarms which may cause
troubles at startup.
VERYIMPORTANT: This must be done for each slave
board.
MultipleEvaporatorConguration(Master/slave)
Up to 4 evaporators can be connected as a
master/slave conguration. DONOTremovetheroom
sensorfromanyoftheBeaconIIboards.
This also applies when connected to the optional Smart
Controller.
PROGRAM
REVIEW
SELECT