HP (Hewlett-Packard) A0554832 Refrigerator User Manual


 
2-40 HP Portable Chillers Chapter 2: Functional Description 10 of 78
2-3 Standard Features
Mechanical Features
Compressor. Hermetic scroll compressors are used on 2 hp through 30 hp (1.49 through
23.37 kW) models. Semi-hermetic discus compressors are used on the 35 hp and 40 hp (26.20
and 29.83 kW) models.
Evaporator. Stainless steel copper brazed plate evaporators are used on 2 hp through 30 hp
models. Shell and tube evaporators are used on the 35 hp and 40 hp models.
Air-Cooled Condenser. Aluminum fin/copper tube with washable filters, package unit only.
Water-Cooled Condenser. 2 hp to 7.5 hp models use tube-in-tube condensers. 10 hp to 40
hp use cleanable shell and tube condensers. All come with cooling water regulating valves
for cooling tower water or city water.
Remote Air-Cooled Condenser. 5 hp to 50 hp only. Aluminum fin/copper tube with low
ambient control down to –20ºF (-29ºC) via pressure-actuated fan staging and a variable-speed
primary fan.
Reservoir. 2 hp and 3 1/2 hp models use a 6 gallon polyethylene tank. 5 hp and 7.5 hp
models use a 20 gallon polyethylene tank. 10 hp and 15 hp models use a 40 gallon
polyethylene tank. 20 hp to 30 hp models use an 80 gallon polyethylene tank, and 35 hp and
40 hp models use an 80 gallon stainless steel tank.
Piping. Non-ferrous piping for 2 hp through 30 hp models. 35 hp and 40 hp models have
ferrous piping.
Pump. Non-overloading ODP motors, horizontally mounted stamped stainless steel or cast
bronze construction.
Other Mechanical Features
External fill/drain sight glass
Low process water pressure switch on 2 hp and 3 1/2 hp models
Low process water flow switch on 5 hp to 40 hp models
Galvanized steel mounting rails for remote air-cooled models
NEMA-rated fan motor(s) on air-cooled models
Galvanized structural steel frame, painted cabinetry, with 2 1/2” swivel casters on 2 hp
and 3 1/2 hp models. 4” swivel casters on 5 hp to 15 hp models, and 5” swivel casters
with brake on 20 hp to 40 hp models.
Valved process water connections
Pressure-actuated process water bypass valve for system protection only; on single
pump models only
To process 2 1/2” dual scale liquid-filled water pressure gauge
Fully insulated refrigeration and process water piping
Isolated fan section on air-cooled models, allowing chiller to run during maintenance
20 mesh Y strainer on process water piping into the evaporator