2-40 HP Portable Chillers Chapter 7: Appendix 60 of 78
Water Pressure Drop Tables
Note: A recirculation pump is required for flows greater than the
maximum or less than the minimum indicated.
Note: Process flow less than or greater than the flow rates shown below
requires a recirculation pump.
Pressure drops in P, psig and kPa
2 HP 3.5 HP 5 HP 7.5 HP
Flow
P
Flow
P
Flow
P
Flow
P
gpm lpm psig kPa gpm lpm psig kPa gpm lpm psig kPa gpm lpm psig kPa
4.06
15.4
3.5
24.1
8.03
30.4
4.0
27.6
10.0
37.9
1.5
10.5
12.0
45.4
2.3
16.1
6.01
22.8
7.0
48.3
10.00
37.9
6.5
44.8
12.0
45.4
2.2
14.8
16.0
60.6
2.9
20.1
8.02
30.4
11.5
79.3
12.00
45.4
10.0
69.
18.0
68.1
4.7
32.1
20.0
75.7
5.0
34.5
10.00
37.9
18.0
124.1
14.00
53.0
13.0
89.6
24.0
90.8
7.3
50.2
24.0
90.8
6.9
47.4
16.00
60.6
18.0
124.1
28.0
106.0
9.6
65.9
33.0
124.9
12.7
87.8
10 HP 15 HP 20 HP 25 HP
Flow
P
Flow
P
Flow
P
Flow
P
gpm lpm psig kPa gpm lpm psig kPa gpm lpm psig kPa gpm lpm psig kPa
22.0
83.3
4.7
32.6
30.0
113.6
4.5
31.3
40.0
151.4
4.0
27.6
55.0
208.2
5.5
37.9
30.0
113.6
8.28
57.1
40.0
151.4
7.5
51.7
45.0
170.3
4.0
27.6
58.0
219.5
5.8
40.0
38.0
143.8
12.91
89.0
50.0
189.3
12.4
85.2
50.0
189.3
5.0
34.5
61.0
230.9
6.0
41.4
46.0
174.1
16.77
115.6
60.0
227.1
17.8
122.8
52.0
196.8
6.0
41.4
70.0
264.9
8.5
58.6
50.0
189.3
20.00
137.9
70.0
264.9
24.2
166.6
55.0
208.2
6.5
44.8
30 HP 35 HP 40 HP
Flow
P
Flow
P
Flow
P
Flow
P
gpm lpm psig kPa gpm lpm psig kPa gpm lpm psig kPa gpm lpm psig kPa
72.0
272.5
6.0
41.1
38.7
146.5
1.5
10.4
92.6
350.5
7.9
54.5
44.7
169.2
2.0
13.8
75.0
283.9
6.5
44.8
51.2
193.8
2.6
17.9
107.1
405.4
10.4
71.7
58.5
221.4
3.4
23.4
80.0
302.8
8.0
55.2
62.3
235.8
3.8
26.2
70.9
268.3
4.9
33.8
85.0
321.7
9.5
65.5
71.8
271.7
4.9
33.8
81.6
308.8
6.3
43.5
82.9 313.7 6.5 44.8
105.7
400.0
10.3
71.0
Note: These pressure drop values are valid for single- and no-pump
portable chillers.
Calculating Chiller Nominal Flow and Pressure to Process
Flow rate: Obtain the flow reading from the appropriate pump curve.
Pressure: Obtain a corresponding pressure reading from the pump curve you selected,
then subtract the one-pump pressure drop listed in the above table using the
appropriate chiller hp and flow rate.
For two-pump (Process/Recirc) chillers, do not subtract pressure drop from table above
for process pump.