OV500 SERIES RACK OVEN - SERVICE PROCEDURES AND ADJUSTMENTS
3. Set oven temperature to 450EF (230°C.) with a
burner flame established, take combustion
measurements O
2
and CO readings.
O
2
: ( Range 6% to 10%)
CO: Not to exceed 0.04% (400PPM)
A. If readings can not be obtained, adjust the
draft inducer baffle and retest for
combustion.
NOTE: If combustion readings still can not be
obtained, contact Bakery Support.
DRAFT INDUCER TEST
1. Access the component panel area for single
point venting and for dual point venting access
draft diverter above oven.
2. Single point venting connect incline manometer
or equivalent to draft inducer tubing. For dual
point venting insert incline manometer tube 6"
above draft diverter.
SINGLE POINT VENTING
F25361 (January 2010)Page 39 of 60