Honeywell PCR-300 Refrigerator User Manual


 
14
The time is entered in increments
of 10 minutes in each case .
Important: The times must be entered
in ascending order.
E03 Alarm temperature difference –50 K to + 50 K 20 K
E04 Delay time – Alarm 0 to 99 mins. 10 mins.
E05 Compressor start-up delay 0 to 15 mins. 5 mins.
E06 Defrost type 1 or 2 1
1 = Electrical (compressor off)
2 = Hot gas (compressor on)
E07 Defrost limit temperature 0 to 50 °C 8 °C
E08 Defrost time limit 1 to 99 mins. 25 mins.
E09 Drainage time, evaporator 0 to 99 mins. 3 mins.
E10 Time delay, fan 0 to 500 secs. 30 secs.
E11 Evaporator fan control 1,2 or 3 1
1 = Fan with compressor.
2 = Continuous fan operation, except during defrosting.
3 = Fan run-on. If there is an undershoot in the cold
store temperature, the fan is switched on by
evaporator sensor T2. The fan is switched off again
once the desired cold store temperature is
attained or exceeded.
E12 Minimum permissible –55 °C to E13 –55 °C
cold store temp.
E13 Maximum permissible E12 to +50 °C +50 °C
cold store temp.
E14 Display during defrosting 1,2 or 3 1
1 = “dEF” in display.
2 = Current cold store temperature in display.
3 = Retaining temperature in display when defrosting
is initiated until the current cold store temperature
reaches the retained value again. This is for a maxi-
mum of 15 minutes after the end of defrosting.
( Evaporator drainage time E09 and time delay fan E10 are not
respected at hot gas defrost mode E06 = 2.