20
Fig. 8b
KM-1900S_H3
KM-1900S_H
Fig. 8a
•Onsinglephasemodels,thewhiteleadmustbeconnectedtotheneutralconductorof
the power source. CAUTION! Miswiring may result in severe damage to the icemaker.
SeeFig. 8a.
•Onthreephasemodels,thetransformer’svoltagetapswitchmustbepositionedtomatch
incoming voltage at startup. See Fig. 8b.
•CAUTION! On three phase models, connect the highest incoming voltage supply
("stinger leg") to the red power supply wire (red common wire to the compressor).
•Theopeningforthepowersupplyconnectionis7/8"DIAtota1/2"tradesizeconduit.