is complete. The pump-out frequency control (S4 dip switch 5 & 6) is factory set, and
generally no adjustment is required. However, the pump-out frequency control can be
set to have a pump-out occur every cycle, or every 2, 5, or 10 cycles. For details, see
"III.C.4. Pump-Out Frequency Control (S4 dip switch 5 & 6)."
Pump-Out Diagnosis: In the freeze cycle before pump-out (see table above), after
5min. of freeze disconnect CB black K5 connector (FS connector). Check that PM
stops and re-starts and that PM rotation is correct (water owing down the drain through
CV). If PM does not stop and re-start, check that CB LEDs 1, 3, and 2 are on. If not,
replace CB. IfLEDs1,3, and 2 are on and PM does not energize, check for 115VAC
at CB K1 #5 (DBU) to neutral (W). If 115VAC is not present, replace CB. If 115VAC
is present, check that X10 relay is de-energized. If not, check X11 relay status. If X11
relay is energized, replace CB. If X11 relay is de-energized and X10 relay is energized,
replace X11 relay (contacts sticking). If X10 relay is de-energized, check for 115VAC
at terminal #6 (DBU) to neutral (W) and terminal #2 (DBU) to neutral (W). If 115VAC is
present on terminal #6 (DBU) and not on terminal #2 (DBU), replace X10 relay. If PM is
energized and rotating in pump-out rotation, make sure the drain line is not clogged and
that CV is clean and operating properly.
Conrm FM and LLV de-energize. If FM or LLV are energized with LEDs 1, 3, and 2 on,
replace CB.
8) Normal Harvest Cycle – Same as the initial harvest cycle. Return to step 5a) above.
Note: Appliance continues to cycle until MBC is satised or power is switched off. The
appliance always restarts at the 1-min. ll cycle.
9) Shutdown
Mechanical Bin Control:
See "II.D.2. Mechanical Bin Control Check."
Legend: CB–control board; Comp–compressor; CV–check valve; FM–fan motor;
FMR–fan motor remote; FS–oat switch; HGV–hot gas valve; HM–headmaster
(C.P.R.); HPS–high-pressure switch; LLV–liquid line valve; MBC–mechanical
bin control; PM–pump motor; TXV–thermostatic expansion valve; WRV–water
regulating Valve; WV–inlet water valve