Freeze Cycle
Average Discharge Pressure
·
A/C: 100 to 155 PSIG
Suction Pressure
·
End Freeze Cycle: 0 to 1.5 PSIG
Refrigerant Metering Device:
·
Capillary tube
Refrigerant Charge (R-134a)
·
9.5 oz.
The thermostat sensing bulb is located into a
plastic tube (bulb holder) secured by two clips
directly to the evaporator serpentine. This control
determines the length of the freezing cycle and
correspondingly the size of the cubes.
A lower setting will produce a larger cube
(oversize) while a higher setting a smaller cuber
(shallow size).
When closed on contacts 3-2 it activates the
defrost or harvest cycle components. The cube
size control is pre-set at the factory (knob in the
black dot position) and doesn’t require any
adjustment when the ambient temperature remains
between 15
o
C and 30
o
C (60
o
F and 90
o
F).
Fan Motor
The fan motor is electrically connected in parallel
to the water pump and it operates continuously
only during the freezing cycle keeping the proper
head pressure by circulating air through the
condenser fins.
Compressor
The hermetic compressor is used to circulate
refrigerant throughout the entire system. It
compresses the low pressure refrigerant vapor
causing its temperature to rise and become high
pressure hot vapor (hot gas) which is then
released through the discharge valve.
Water Spray System
Sprays the water into each individual cup to be
frozen into ice.
ICEU070A
Page 10