Manitowoc Ice STH003 Ice Maker User Manual


 
51
SUCTION PRESSURE HIGH CHECKLIST
Problem
Cause
Improper Installation
Refer to “Installation/Visual Inspection Checklist”
Discharge Pressure
Discharge pressure is too high, and is affecting
suction pressure, refer to “Freeze Cycle Discharge
Pressure High Checklist”
Improper Refrigerant Charge
Overcharged
Wrong type of refrigerant
Non Condensable in system
Other
Non-Manitowoc components in system
Hot gas valve leaking
Defective compressor
Water inlet valve leaking
SUCTION PRESSURE LOW CHECKLIST
Problem
Cause
Improper Installation
Refer to “Installation/Visual Inspection Checklist”
Discharge Pressure
Discharge pressure is too low, and is affecting
suction pressure, refer to “Freeze Cycle Discharge
Pressure Low Checklist”
Improper Refrigerant Charge
Undercharged
Wrong type of refrigerant
Other
Non-Manitowoc components in system
Improper water supply over evaporator refer to
“Water System Checklist”
Loss of heat transfer from tubing on back side of
evaporator
Restricted/plugged liquid line drier
Restricted/plugged tubing in suction side of
refrigeration system
NOTE: Do not limit your diagnosis to only the items
listed in the checklists.