REPLACING PRESSURE CONTROLS
WITHOUT REMOVING REFRIGERANT
CHARGE
This procedure reduces repair time and cost. Use it
when any of the following components require
replacement, and the refrigeration system is
operational and leak-free.
Fan cycle control
High pressure cut-out control
High side access valve
Low side access valve
IMPORTANT
This is a required in-warranty repair procedure.
1. Disconnect power to the ice machine.
2. Follow all manufacturers’ instructions supplied with
the pinch-off tool. Position the pinch-off tool
around the tubing as far from the pressure control
as feasible. (See the figure on next page.) Clamp
down on the tubing until the pinch-off is complete.
WARNING
Do not unsolder a defective component. Cut it out of
the system. Do not remove the pinch-off tool until
the new component is securely in place.
3. Cut the tubing of the defective component with a
small tubing cutter.
4. Solder the replacement component in place. Allow
the solder joint to cool.
5. Remove the pinch-off tool.
6. Re-round the tubing. Position the flattened tubing
in the proper hole in the pinch off tool. Tighten the
wing nuts until the block is tight and the tubing is
rounded.
NOTE: The pressure controls will operate normally
once the tubing is re-rounded. Tubing may not re-
round 100%.