Master Bilt TAF-74 ERC2 Refrigerator User Manual


 
11
Minimum
Compressor
On Time
Con Minimum time that
the compressor
remain turned on
Range: from 0 to 15 min 2 min.
Alarm Delay ALrd Time delay before
the alarm goes off
after the
temperature fall
off the two alarm
set points
Range: from 0 to 59 min 30 – for LT
45 – for MT
Compressor
Run Time
CPrn Time the
compressor runs
between defrosts
12 – for MT
Number of
Defrosts
nodF Number of defrosts
per day
from 0 to 8 (0 means 1 defrost
every 48 hours)
N/A – for LT
0 – for MT
Defrost Start
Time
dEF1-8 Start time of each
defrost
N/A
Defrost
Duration
dEFd Defrost duration
time (back-up for
defrost
termination
temperature)
Range: from 0 min to 4 hours 35 – for LT
0 – for MT
Fan Delay FAnd Delay time for the
fan after defrost
(back-up for fan
cut-in
temperature)
Range: from 0 to 15 min 2 – for LT
0 – for MT
Pump Down Pudn Pump down duration
Range: from 0 to 59 min 0 min.
Drip Time driP Drip time duration Range: from 0 to 59 min 2 – for LT
0 – for MT
Setpoint
Differential
diF°
Cut-in temperature
differential
Note: cut-in is cut-
out plus differential
Range: from 1 to 25° 10° F–for LT
7
o
F – for MT
Temperature
Initiated
Defrost
tdEF Temperature that
will initiate a
defrost cycle
Range: from – 40 to 40°F or – 40 to
4°C
N/A
Defrost
Termination
Temperature
dEF°
Temperature in the
evaporator that
will terminate the
defrost cycle
Range: from 0 to 75°F or –18 to
25°C
50° F
Fan Cut-In
Temperature
FAn°
Temperature in the
evaporator that
will turn the fan
on after defrost
Range: from – 40 to 60°F or – 40 to
23°C
30° F–for LT
60
o
F–for MT
Low
Temperature
Alarm
ALLo
Low temperature
setpoint that will
make the alarm go
off and the error
message appear on
the display
Range: from – 40 to 83°F or – 40 to
23°C
-40° F–for LT
32
o
F–for MT