3.2.2 Installation location
Required water sources
Table 3-1 Heat Discharge and Required Quantity of Facility Water (HRG010-W, HRG015-W)
Model
Heat discharge
(kW)
Facility water temp. range (°C)
Required water
quantity (L/min)
HRG010-W Approx. 16 34
HRG015-W Approx. 23
5 to 32
(Rated temp.: 25)
40
Outside installation
HRG010 and HRG015 are IPx3-compliant rainproof systems but not rendered complete
waterproof. Install the system out of direct sunlight as well as direct rain and snow (e.g. under
the eaves).
A water-refrigerated thermo cooler is designed to exhaust heat
through a supply of facility water.
Secure water sources listed below.