Instructions for the Installer
parts are placed in the correct position.
When the installation is completed the installation
connections of cooker will require to be leak tested, the
burner operating pressure and flame checked and
adjusted.
Warranty service calls do not cover these adjustments!
To check the operating pressure of the appliance it is
recommended at least 2 large size burners are used.
Ensure appliance is secured to wall when installation is
completed.
N.G. The regulator supplied must be fitted to the ½
BSP thread at the rear of the appliance. An approved
manual shut-off valve must be installed. The N.G.
regulator must be checked and adjusted to 1.0kPa
after installation.
L.P.G. Can be connected to the inlet fitting directly.
The pressure must be checked to ensure it is operating
at 2.75kPa. A separate test point fitting must be
installed between the piping & the appliance for the
pressure to be checked to ensure it is operating at
2.75kPa.
2.4 Room ventilation
Caution – This cooker may only be installed and operated in rooms
permanently ventilated in accordance with current regulations. For
proper operation of a gas appliance it is essential for the air necessary
for combustion of the gas to be able to flow naturally into the room. Air
must flow directly into the room through openings in its outside walls.
This (these) opening (s) must have a free passage cross-section of at
least 100 cm
2
, or 200 cm
2
for appliances not equipped with gas safety
device. These openings must be constructed so that they cannot be
obstructed indoors or outdoors, and should preferably be close to the
floor on the side opposite to the combustion gas discharge point. If it is
not possible to make the openings in the room where the cooker is
installed, the necessary air may be taken from an adjoining room,
proveded it is not a bedroom or a room with fire risk.
9