3. Installation
Make sure the location satisfied the requirements listed under Storage and Installation
Location (page 3) and check the dimensions using the diagrams in other catalogs or external
view diagrams and panel cut diagram. Prior to installation, the maximum fault current capacity
of the power system at the point of installation should be verified. This value must not exceed
the symmetrical interrupting capability of the circuit breaker. See typical circuit breaker
nameplate below.
Do not exceed the ratings specified on the breaker nameplate or
system accessories. Underrated equipment can fail during operation
causing fire, explosion, severe injury, death, and property damage.
Typical Circuit Breaker Nameplate
3.1 Mounting the VCB
3.1.1 Mounting in the panel
The standard panel thickness is t3.2. Consult Toshiba when using with other thicknesses.
To mount the VCB, perform the steps shown in Figures 8 through 10 in that order, referring
to the tightening torque in Table 5.
Figure 7 Remove the four (4) panel
mounting bolts (M8) and two (2) pan-head
screws (M4) from the VCB.
Figure 8 Align to the panel holes
and mount the VCB with two (2)
upper bolts on the panel.
DANGER