Toshiba HV6FS-MLD Tortilla Maker User Manual


 
PRE-ENERGIZATION CHECK Page 21
MANUAL OPERATION
Powerful springs. Do not
place your hands or any
part of your body inside
the circuit breaker while
the indicators show
CHARGED (yellow) or ON
(red).
To avoid damaging the
mechanism, do not close
the circuit breaker when
the On-Off Indicator shows
ON (red).
MANUAL CLOSING:
1. Check to make sure that the On-Off
indicator shows OFF (green).
2. Attach the charging handle to the breaker if it
is not already attached.
3. If the closing spring status indicator shows
DISCHARGED (white):
Turn the closing handle clockwise 3 to 5
times to charge the closing spring (Fig. 25).
(Closing Spring Status Indicator changes to
CHARGED, Yellow) When the handle is
released, it returns to its normal position, and
do not attempt to turn again. (Fig. 26)
If the closing spring status indicator shows
CHARGED (yellow):
Do not attempt to turn handle.
Pushing the Green lever in the direction of
the arrow closes the circuit breaker (On-Off
indicator changes to ON)
Fig. 25 Preparing to Manually Close Breaker
Fig. 26 Manually Charging Breaker
WARNING
CAUTION
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net