Venmar HRV 2600* Ventilation Hood User Manual


 
5.4 INSTALLING NON-INSULATED DUCTS AND REGISTERS (CONTD)
5.4.2 C
ENTRAL DRAW POINT (AS ILLUSTRATED IN SECTION 1.1.2) (CONTD)
Fresh/Filtered air ductwork (Return side connection) (cont’d)
HEPA 3100, HF 3.1
AND HEPA 4100 UNITS ONLY (CONTD)
Fix the duct connector to the forced air unit duct using its 4 retaining screws (#8 x 3/4” long). Seal
with duct tape.
Take one end of the 8’’ flexible duct and slide it over the duct connector. Secure with a tie wrap.
Carefully seal the connection with duct tape. Identifiy the duct using the blue sticker dot included.
Attach this duct to the
FRESH AIR TO BUILDING
port (see icon on the top of the unit), using tie wrap and
duct tape.
5.4.3 R
ETURN-TO-RETURN (AS ILLUSTRATED IN SECTIONS 1.1.3 AND 1.2.2)
Fresh/Filtered air ductwork (Return side connection)
Same as for Central Draw Point, described in point 5.4.2.
Stale air ductwork (Return side connection)
A
LL UNITS
Locate the stale air ductwork opening at least 3’ (0.9 m) from the fresh/filtered air ductwork
connection. For the HRV 2600 and HR 2.6 units, use a steel transition (not provided, available
in hardware stores). Proceed as for the fresh/filtered air ductwork, but instead of using the blue
dot sticker to identify the duct, use the red dot. (No dots for HRV 2600 and HR 2.6 units.)
Attach this duct to the
EXHAUST AIR FROM BUILDING
port (see icon on the top of the unit), using tie wrap
and duct tape.