Wells WFAE-30F Fryer User Manual


 
ELECTRICAL INSTALLATION
Refer to the nameplate on the front of the fryer and to the specifications
listed on page 1 of this manual. Verify that electric service voltage,
phase and amperage capacity meet or exceed these specifications.
Field wiring must be no less than 12 ga. Solid copper wire, rated for at
lease 75ºC.
Fryers are shipped from the factory wired for 3Ø. Verify that field wiring
conforms to the Three-Phase Wiring Diagram included with the fryer.
NOTE: Fryers are FIELD-CONVERTIBLE TO 1Ø. For single-phase
operation refer to the 3-phase to 1-phase Instructions included with the
fryer. Verify that both internal wiring and field wiring conforms to the
Single-Phase Wiring Diagram included with the fryer.
IMPORTANT:
Field wiring must be routed and secured away from the FRYPOT,
TUBING and FILTER PUMP MOTOR. Field wiring must be configured
to allow access to the rear of fryer for cleaning and access to the filter
pump motor RESET BUTTON.
INSTALLATION (continued)
7
IMPORTANT:
Electric installation of this
appliance must be performed
by a licensed electrician.
Installation must conform to
the requirements of local
codes and ordinances, as
well as to the requirements of
the National Electrical Code.
Fig. 2 Field Wiring
361 301669 OpManual for WFAE-30F Electric Fryer
FRYPOT
CONDUIT
FITTING
90º
FILTER
PUMP &
MOTOR
POWER
CORD