USE AND MAINTENANCE SHALL BE IN ACCORDANCE WITH THE
STANDARD FOR VENTILATION CONTROL AND FIRE PROTECTION
OF COMMERIAL COOKING OPERATIONS, N.F.P.A. 96 (current
edition).
3-MONTH MAINTENANCE:
Thoroughly clean entire HOOD PLENUM and BLOWER section.
6-MONTH MAINTENANCE:
Inspection and testing of total operation including FIRE DAMPER and
all SAFETY INTERLOCKS shall be performed by qualified service
personnel.
All FIRE SUPPRESION SYSTEM actuation components including
MANUAL PULL STATION and any REMOTE MANUAL PULL STATION
must be inspected for proper operation in accordance with the
maintenance schedule published in
ANSUL® R-102 SYSTEM DESIGN,
INSTALLATION, RECHARGE AND MAINTENANCE MANUAL (418087).
On WVAE-Model fryers, open the rear cover access door
and lubricate the LIFT WORM threads with molybdenum disulfide
grease (see item v.15 page 2) .
ANNUAL (12-MONTH) MAINTENANCE:
FIRE SUPRESSION SYSTEM FUSIBLE LINKS must be replaced.
NOZZLES and MANUAL PULL STATION must be cleaned in
accordance with
ANSUL® R-102 SYSYTEM DESIGN, INSTALLATION,
RECHARGE AND MAINTENANCE MANUAL (418087).
12-YEAR MAINTENANCE:
The FIRE SUPRESSION AGENT TANK and ¼” FLEX HOSE must be
HYDROSTATICALLY TESTED, and the FIRE EXTINGUISHING
AGENT must be REPLACED in accordance with the maintenance
schedule published in ANSUL® R-102 SYSTEM (STANDARD UL 300
LISTED). This maintenance to be performed by qualified Ansul®
service personnel only.
REQUIRED MAINTENANCE
14
IMPORTANT:
A signed and dated FRYER
HOOD MAINTENANCE LOG
must be maintained on the
premises, and shall be made
available for inspection by the
authority having jurisdiction
upon request.
See page 15.
M381 301603 OpM (Supplemental) NFPA Hood