Electrical Data
MULTIPOINT POWER SUPPLY (SEE FIG 9 , PAGE 30)
SYSTEM #1
(Each of the two field provided power supply circuits individually protected with branch circuit protection. Field
connections to factory provided Terminal Block(std), Non-Fused Disconnects(opt) or individual system Circuit
Breakers(opt) in each of the two motor control centers.)
YCWS0100SC 175 200 225 300 140 404
YCWS0120SC 175 200 225 300 140 404
YCWS0140SC 227 250 300 400 181 591
YCWS0180SC -17 227 250 300 400 181 591
YCWS0200SC 284 400 350 500 227 708
YCWS0220SC 284 400 350 500 227 708
YCWS0240SC 337 400 450 600 269 708
YCWS0100SC 153 150 200 250 122 354
YCWS0120SC 153 150 200 250 122 354
YCWS0140SC 198 200 250 350 158 481
YCWS0180SC -28 198 200 250 350 158 481
YCWS0200SC 247 250 300 400 197 642
YCWS0220SC 247 250 300 400 197 642
YCWS0240SC 293 400 400 500 234 642
YCWS0100SC 93 100 125 150 74 219
YCWS0120SC 93 100 125 150 74 219
YCWS0140SC 120 150 150 200 96 285
YCWS0180SC -40 120 150 150 200 96 285
YCWS0200SC 149 150 200 250 119 343
YCWS0220SC 149 150 200 250 119 343
YCWS0240SC 177 200 225 300 141 343
YCWS0100SC 77 100 100 125 61 174
YCWS0120SC 77 100 100 125 61 174
YCWS0140SC 99 100 125 175 79 228
YCWS0180SC -46 99 100 125 175 79 228
YCWS0200SC 123 150 150 200 98 280
YCWS0220SC 123 150 150 200 98 280
YCWS0240SC 147 150 200 250 117 280
YCWS0100SC 62 60 80 110 49 138
YCWS0120SC 62 60 80 110 49 138
YCWS0140SC 79 100 100 125 63 182
YCWS0180SC -58 79 100 100 125 63 182
YCWS0200SC 99 100 125 150 79 224
YCWS0220SC 99 100 125 150 79 224
YCWS0240SC 118 150 150 200 94 224
CHILLER
MODEL
VOLT
CODE
HZ
MIN NF
DISC SW
MIN
(1)
CIR.
MCA
MIN
DUAL
FUSE
MAX DUAL
FUSE
MAX CB
RLA
Y-D
LRA