Aprilaire 8100 Ventilation Hood User Manual


 
SPECIFICATIONS
Dimensions
Unit – 37-7/16” W x 12-3/4” D x 20-9/16” H
EnergyMax Transfer Core – 12-1/8” x 12-1/8” x 10-3/4”
Weight
75 lbs.
Performance
77% Apparent Sensible Effectiveness (ASE)
At rated ventilation capacity with 72°F indoor temperature and 32°F outdoor temperature.
Capacity
Maximum home size per ASHRAE Standard 62.2-2010* with continuous operation at rated airflow:
4-5 bedrooms – 7,500 ft
2
, 6-7 bedrooms – 6,000 ft
2
, 7+ bedrooms – 4,500 ft
2
.
*No infiltration credit assumed. Refer to the standard for details on required ventilation rates.
Power
120 VAC, 1.4 Amp maximum. Unit equipped with 3 ft. grounded power cord.
Filter
Two 10-13/16” x 11-5/16” x 3/32” EZ Kleen air filters. Filters coated with Super Filter Coat adhesive.
Airflow
120 cfm at 0.30” w.c. external pressure.
UNPACKING AND CONTENTS
1. Open one end of the carton.
2. Remove the cardboard inner pack.
3. See Figure 1 for carton contents.
a. Inner pack
b. Energy Recovery Ventilator
c. Installation Instructions
d. Owner’s Manual
e. Mounting Hardware Carton
4. See Figure 2 for contents of mounting
hardware carton.
a. Mounting Bracket
b. Hanging Hook Bracket
c. Hanging Hinge Bracket
d. Hanging Pins and Threaded Nuts
e. Machine Screws
f. Lag Bolts and Washers
ENERGY RECOVERY VENTILATOR
MOUNTING HARDWARE
INSTALLATION MANUAL
OWNERS MANUAL
INNER PACK
WASHERS
LAG BOLTS
MACHINE SCREWS
THREADED NUTS
HANGING PINS
MOUNTING BRACKET
HANGING HOOK BRACKET
HANGING HINGE BRACKET
FIGURE 1 – Opening View and Contents
FIGURE 2 – Mounting Hardware
90-1751
90-1739
2