Carrier 30HXA Water Dispenser User Manual


 
30HXA REFRIGERANT PIPING (See Fig. 7) Take
care when running the refrigerant piping from the 30HXA
unit to the remote condenser(s) to avoid excessive pres-
sure drops. The pressure drop using R-134a refrigerant is
different than when using R-22 refrigerant. See Tables 2 and
3 for an example fora2F(1.1 C) pressure drop in saturated
temperature in the discharge (hot gas) line and liquid line,
respectively. Refer to Fig. 9 and 10 for line sizing informa-
tion for the discharge and liquid lines for 30HXA (R-134a)
units.
Table 2 Discharge Line 2 F (1.1 C) Drop in
Saturated Temperature Example
SATURATED
DISCHARGE
TEMP
PRESSURE
R-134a R-22
F C Psig kPa Psig kPa
126 52.2 187.5 1293 281.6 1942
124 51.1 182.0 1255 274.3 1891
PRESSURE 5.5 38 7.3 51
PRESSURE
RELIEF
DISCHARGE
LINE
LIQUID LINE
LIQUID LINE
ANGLE
VALVE
OIL
SEPARATOR
COOLER*
TO REMOTE
CONDENSER(S)
TO REMOTE
CONDENSER(S)
TO REMOTE
CONDENSER(S)
TO REMOTE
CONDENSER(S)
EXV
EXV
Fig.7—Typical 30HXA Refrigerant Piping to Remote Condenser
NOTES:
1. Piping shown is for general point-of-connection only and is not in-
tended to show details for a specific installation. Certified field wir-
ing anddimensional drawings areavailable uponrequest. The30HXA
units should be installed using certified drawings.
2. Refer to Carrier System Design Manual for details regarding pip-
ing techniques.
3. Piping and pressure relief devices are field supplied.
4. Vent pipes properly per local codes.
LEGEND
EXV Electronic Expansion Valve
*See Fig. 6 for typical cooler piping.
LEGEND
COM Common
N.O. Normally Open
Fig. 8 Differential Flow Switch
11