50
Table 2 — Electrical Data Without VAV Option (cont)
LEGEND
*Fused disconnect only.
†Exhaust and supply fan motors are 230-1-60.
UNIT SIZE
62M
VOLTAGE
(V-Ph-Hz)
ERV WHEEL
FLA
EXHAUST AND SUPPLY MOTOR
HEATER
SIZE
(kW)
POWER SUPPLY
PRE-HEATER
(Optional)
FLA
DISCONNECT
(Optional)
NEC - FLA Hp FLA MCA MOCP
Amps
Fuse Size†
Amps
640
208/230-3-60
1.2
22
7.5
— 45.53 56.50 72.70 — 100 70
8 65.64 81.63 92.81 20.11
200
90
10 70.66 87.91 97.83 25.13
15 83.23 103.62 110.40 37.70 110
460-3-60 11
— 22.82 29.00 36.95 —
60
35
8 32.87 41.57 47.00 10.05
45
10 35.38 44.71 49.52 12.57 60
15 41.66 52.56 55.80 18.85 80 50
575-3-60 9
— 18.65 24.00 30.45 — 40 30
8 26.69 34.05 38.49 8.04
60
35
10 28.70 36.57 40.50 10.05 40
15 33.73 42.85 45.53 15.08 45
750
208/230-3-60 2.5 22
— 46.83 58.13 74.00 — 100 70
10 71.96 89.54 99.13 25.13
200
90
15 84.53 105.25 111.70 37.70
110
20 97.09 120.95 124.26 50.26
460-3-60 1.2 11
— 23.36 29.00 36.95 —
60
35
10 35.93 44.71 49.52 12.57 45
15 42.21 52.56 55.80 18.85 80 50
20 48.49 60.41 62.08 25.13 80 60
575-3-60 1.4 9
— 19.53 24.25 30.65 — 40 30
10 29.58 36.82 40.70 10.05
60
40
15 34.61 43.10 45.73 15.08 45
20 39.64 49.38 50.76 20.11 50
950
208/230-3-60 2.5 30.8
10
— 64.46 80.13 102.60 —
200
100
10 92.25 114.86 130.39 27.79
125
15 106.15 132.23 144.29 41.69
20 120.04 149.60 158.18 55.58 N/A
460-3-60 1.2 14
— 29.36 36.50 46.70 — 60 45
10 41.93 52.21 59.27 12.57 80 50
15 48.21 60.06 65.55 18.85 80 60
20 54.49 67.91 71.83 25.13 100 70
575-3-60 1.4 11
— 23.53 29.25 37.15 —
60
35
10 33.58 41.82 47.20 10.05 45
15 38.61 48.10 52.23 15.08
80 50
20 43.64 54.38 57.26 20.11
ERV — Energy Recovery Ventilator
FLA — Full Load Amps
Hp — Horsepower
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC — National Electric Code
N/A — Not Applicable