Carrier 62ME Ventilation Hood User Manual


 
53
Table 3 — Electrical Data With VAV Option (cont)
LEGEND
*The VAV option is not available on 62M040 units.
†Fused disconnect only.
**Exhaust and supply fan motors are 230-3-60.
UNIT SIZE
62M*
VFD
VOLTAGE
V-Ph-Hz
ERV
WHEEL
FLA
VFD
CURRENT
INPUT
VALUE
AMP
EXHAUST AND SUPPLY
FAN MOTOR HEATER
SIZE
(kW)
POWER SUPPLY PRE-
HEATER
(Optional)
FLA
DISCONNECT
(Optional)
NEC - FLA Hp FLA MCA MOCP Amps
Fuse Size†
Amps
640
208/230-3-60
1.2
26 22
7.5
53.61 65.10 84.64 100 80
8 73.72 90.24 104.74 20.11
200
100
10 78.75 96.52 109.77 25.13 100
15 91.31 112.23 122.33 37.70 110
460-3-60 12.9 11
26.65 32.29 41.98
60
40
8 36.70 44.86 52.03 10.05 50
10 39.21 48.00 54.55 12.57
80
50
15 45.50 55.85 60.83 18.85 60
575-3-60 11.5 9
23.62 28.71 37.33
60
35
8 31.66 38.76 45.37 8.04 45
10 33.67 41.28 47.38 10.05 45
15 38.70 47.56 52.40 15.08 80 50
750
208/230-3-60 2.5 26 22
54.91 65.10 84.64 100 80
10 80.05 96.52 109.77 25.13
200
100
15 92.61 112.23 122.33 37.70 110
20 105.18 127.93 134.90 50.26 125
460-3-60 1.2 12.9 11
27.20 32.29 41.98 60 40
10 39.76 48.00 54.55 12.57
80
50
15 46.05 55.85 60.83 18.85 60
20 52.33 63.71 67.11 25.13 60
575-3-60 1.4 11.5 9
24.50 28.71 37.33
60
35
10 34.55 41.28 47.38 10.05 45
15 39.58 47.56 52.40 15.08
80
50
20 44.61 53.84 57.43 20.11 50
950
208/230-3-60 2.5 34 30.8
10
70.86 85.00 110.50
200
110
10 98.65 119.74 138.29 27.79 125
15 112.55 137.11 152.19 41.69 N/A
20 126.44 154.48 166.08 55.58 N/A
460-3-60 1.2 16.5 14
34.28 41.15 53.49
80
50
10 46.85 56.85 66.06 12.57 60
15 53.13 64.71 72.34 18.85 70
20 59.41 72.56 78.62 25.13 100 70
575-3-60 1.4 14 11
29.63 35.12 45.66 60 45
10 39.68 47.69 55.71 10.05
80
50
15 44.71 53.97 60.74 15.08 60
20 49.73 60.25 65.76 20.11 60
ERV Energy Recovery Ventilator
FLA Full Load Amps
Hp Horsepower
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
NEC National Electric Code
N/A Not Applicable
VFD Variable Frequency Drive