Cascade TFO-10 Oven User Manual


 
F O R C E D A I R O V E N M A N U A L
Cascade TEK 5245-A NE Elam Young Parkway Hilllsboro Oregon 97124
Toll Free 888-835-9250 503-648-1818 FAX 503-648-1798 info@cascadetek.com www.cascadetek.com
REV 01.08
18
8.1 Watlow Controller Settings: Refer to Section 1-2 of Watlow Manual
These are internal controller default settings pre-set at the factory for optimum oven
performance. Altering these settings can cause performance problems. Please
contact Customer Service if settings have been altered.
MODE SET TO ALTERNATE
DISPLAY LOWER UPPER UPPER
SET gLbL
C_F C F
Err Nla Nla
eI1 NO NO
ANUN ON ON
LOP 0 0
HIP 100 100
ATSP 90 90
PTYP TI Ti
GSD 0 0
POUT CONT CONT
PSTR STPT STPT
LOC 0 0
INPUT
IN1 J J
RL1 0 32
RH1 300 572
CAL1 0 0
FTLR 0 0
OUTPUT
OT1 HT HT
HYS1 2 2
OT3 ENT3 ENT3
Note: The PID Settings for the TFO Ovens are set by running the auto-tune feature
at 150C.