Conversion To LP Gas
RECONNECT GAS AND ELECTRICAL SUPPLY TO
RANGE
Leak testing of the appliance shall be conducted according to the installation
instructions provided with the range.
Checking for Manifold Gas Pressure
If it is necessary to check the manifold gas pressure, remove the burner cap, inner
ring, outer burner head and burner base of the right front top burner and connect a
manometer (water gauge) or other pressure test device to the burner orifice. Use a
rubber hose, and hold the end of the tube tight over the orifice. Turn the gas valve
on. For a more accurate pressure check, have at least two (2) other top burners
burning. Be sure that the gas supply (inlet) pressure is at least one inch above the
specified range manifold pressure. The gas supply pressure should never be over
14” water column. When properly adjusted, the manifold water column pressure is
10” for LP/Propane gas or 5” for Natural Gas.
a. Disconnect the range and its individual shut-off valve from the gas supply piping
system during any pressure of that system at test pressures greater than 14” of
water column pressure.
b. The appliance must be isolated from the gas supply piping system by closing its
individual manual shut-off valve during any pressure testing of the supply system
at test pressure equal to or less than 14” water column pressure.
CACA
CACA
CA
UTIONUTION
UTIONUTION
UTION
Do not use a flame to check for gas leaks