Emerson VH Refrigerator User Manual


 
Advanced Microprocessor Controls Setup
11
Enable Alarms: Each individual alarm can be selected to be ENABLED (annunciated audibly, visu-
ally, and communicated to a Site Products System) or DISABLED (ignored).
Enable Common Alarm: Each individual alarm can be selected to energize or to not energize the
common alarm relay. If the energize common alarm function is set to YES, the relay is energized
immediately as the alarm is annunciated and de-energized when the alarm condition goes away (only
after the alarm has been recognized). If the function is set to NO, the alarm has no effect on the com-
mon alarm relay regardless of whether the alarm is ENABLED or DISABLED.
Set Custom Alarms: The custom alarm messages can be from a list of standard alarm messages or
you can create your own message.
They can be in any location(s) 1 through 4. The text for custom alarms can be changed at any time by
selecting “SET CUSTOM ALARMS”. To change the text for a custom alarm, select “SELECT
ALARM”. Then, select which alarm you would like to change, 1 through 4. Using the UP/DOWN
arrows will step through the list of five standard alarm messages (see Standard Alarm
Messages on page 12) and the two custom alarms.
Press ENTER to make your selection. To modify the two custom alarm messages, go back one screen
and select “CHANGE CUSTOM TXT 1” (or 2). Text can be up to 20 characters in length and can be
any of the following characters (or a blank space):
ABCDEFGHIJKLMNOPQRSTUVWXYZ#%*-0123456789.
Table 5 Alarm default time delay
Alarm Default Delay (seconds)
Humidifier Problem 2
High Head Pressure 1 2
High Head Pressure 2 2
Change Filter 2
Loss of Air Flow 3
Custom Alarm #1 0
Custom Alarm #2 0
Custom Alarm #3 0
Custom Alarm #4 6
High Temperature 30
Low Temperature 30
High Humidity 30
Low Humidity 30
Low Suction Pressure 1, 2 0
Short Cycle 1, 2 0
Compressor #1 Overload 2
Compressor #2 Overload 2
Main Fan Overload 5
Loss of Power 0
NOTE
Only one (1) or two (2) of the alarm messages can be your own message.
NOTE
The two custom alarm message will be shown with what was previously programmed in them
and can be changed.