Component Operation and Maintenance, Checks and Adjustments
63
Figure 12 Steam generating humidifier control board
7.6 Electric Reheat
Table 20 DIP switch settings for steam generating humidifier
Unit Rated
Voltage Capacity SW1 SW2 SW3 SW4
Rated Values
Voltage AMP Set Pt
200/208 11 Off On Off On 208 12.6
200/208 22 On Off On On 208 23.8
230 11 Off Off Off On 240 10.5
230 22 Off Off On On 240 20.3
380/400/415 11 On On Off Off 400 6.3
380/400/415 22 Off On On On 400 12.6
460 11 On Off Off Off 480 5.5
460 22 Off Off Off On 480 10.5
575* 11 Off Off Off Off 575 4.2
575* 22 Off On Off On 575 9.8
*The values are only suitable in models FH600C and FH740C. All other models use a 575 volt to 460 volt step-down
transformer and therefore use the 460V settings.
!
CAUTION
Reheat element sheaths and fins are manufactured with stainless steel. Regular inspections
are necessary to assure proper cleanliness of the reheating element. Should inspection reveal
corrosion particles on the reheating element or adjoining surfaces (including ducts and
plenums), appropriate cleaning should be performed. Periodic reheating element replacement
may be required to meet specific application requirements.