Frymaster FMCFEC Fryer User Manual


 
MASTER JET CF SERIES ATMOSPHERIC GAS FRYERS
CHAPTER 1: SERVICE PROCEDURES
1-6
1.3 Checking Burner Manifold Gas Pressure (cont.)
Non-CE Standard
for Incoming Gas Pressures
Gas Minimum Maximum
Natural
6" W.C.
1.49 kPa
14.93 mbar
14" W.C.
3.48 kPa
34.84 mbar
LP
11" W.C.
2.74 kPa
27.37 mbar
14" W.C.
3.48 kPa
34.84 mbar
Gas
Natural
LP
8.25" W.C.
2.0 kPa
20.0 mbar
Pressure
Non-CE Standard
3.5" W.C.
.75 kPa
7.5 mbar
for Burner Manifold Gas Pressures
4. If the measured manifold gas pressure does not match the appropriate pressure in the preceding
tables, remove the cap from the gas valve regulator and adjust to the correct pressure.
Honeywell Valve
(Non-CE Units)
Honeywell Valve
(CE Units)
Regulator Adjustment Screw Cap
1.4 Adjusting Pilot Flame
1. On non-CE valves, remove the cap covering the pilot adjustment screw. On all valves, turn the
pilot adjustment screw counterclockwise to increase the length of the flame or clockwise to
decrease the length of the flame. Adjust the flame to a length of 1 to 1-½ inches (25 to 38 mm).
Honeywell Valve
(Non-CE Units)
Honeywell Valve
(CE Units)
Pilot Adjustment Screw
On Non-CE gas valves, remove this cap to
access Pilot Adjustment Screw.
2. On Non-CE valves, reinstall the pilot adjustment screw cap.