Electrical connections CONNECTIONS
The appliance must be electrically installed and grounded in accordance with local codes or in
the absence of such codes with the latest edition of the "National Electrical Code",
ANSI/NFPA 70 in the USA, and CSA C22.2 "Canadian Electrical Code" - in Canada.
Disconnect all the power supply circuits before accessing the junction boxes.
This appliance must be supplied with 240 Volt and 60 Hz frequency, and connected to an
individual, properly grounded branch circuit, protected by a circuit breaker or time-delay fuse, as
noted on the rating plate.
Use only a 3-wire or a 4-wire UL-listed power-supply cord rated 120/240 Volts with a straight
terminals and marked for use with ranges.
The specified ampere rating for the cord shall be 20 A.
Only a 4 wire cord is to be used when the appliance is installed where grounding through the
neutral conductor is prohibited, such as:
- new branch-circuit installations (1996 NEC),
- mobile homes,
- recreational vehicles or
- in an area where local codes prohibit grounding through the neutral.
The power of the electric elements for appliance see page 14 and page 17.
The overall wattage of your appliance is also indicated on the nameplate label and on the warranty
certificate (See item 5 page 14 for the location of the nameplate label).
Wiring must conform to National Electric Codes.
If the electric service provided does not meet the above specifications, have a licensed electrician
install an approved outlet.
Because range terminals are not accessible after range is in position, flexible service conduit or
cord must be used at least 4 ft. (1.2 m) length. The range can then be easily disconnected for
servicing.
The CornuFé 1908 - 36" is supplied with a connection terminal block accessible by unscrewing
the stainless steel protection plate on the backside.
1. Remove the screws and the protection plate on the backside of the range.
1. ELECTRICAL CONNECTIONS