PREMIUM CEILING FAN
A
SP
Dimensional Data
Performance Data
Performance certified is for Model SP exhaust for installation type B: Free inlet, Ducted outlet. Performance ratings include the effects of an inlet grille and backdraft damper. Speed
(RPM) shown is nominal. Performance is based on actual speed of test. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated
per AMCA Standard 301. Values are for installation type B: free inlet fan sone levels.
HVI CFM/Static Pressure in inches of WG
Model RPM Amps Watts
Sones 0.000 0.100 0.125 0.250 0.375 0.500 0.625 0.750 1.000
CFM 76 51 47 30
SP-A50 700 0.31 18 0.7
Sones 0.7 1.0 1.1 1.8
CFM 83 70 66 42
SP-A70 850 0.27 20 0.8
Sones 1.1 1.1 1.4 2.2
CFM 99 88 84 61 25
SP-A90 900 0.34 29 1.0
Sones 1.1 1.4 1.4 1.7 1.9
CFM 119 110 106 88
SP-A110 950 0.58 49 0.8
Sones 1.3 1.2 1.2 1.6
CFM 135 123 121 104
SP-A125 1100 0.62 53 1.2
Sones 1.4 1.7 1.8 1.9
CFM 216 197 192 167 133
SP-A190 1400 1.30 113 2.0
Sones 3.2 2.8 2.9 3.1 3.4
CFM 247 225 220 196 172 142 105 67
SP-A200 900 0.43 48 2.0
Sones 2.0 2.3 2.4 3.0 3.5 4.1 4.6 4.5
CFM 272 251 246 227 210 185 157 119
SP-A250 1000 0.77 83 2.0
Sones 2.9 3.0 3.0 3.4 4.4 4.6 4.9 5.2
CFM 315 293 287 257 231 207 175 124
SP-A290 1050 0.72 81 2.5
Sones 3.2 3.3 3.3 3.6 3.9 4.1 4.5 5.5
CFM 410 395 391 368 345 325 307 279
SP-A390 1350 1.34 135 4.5
Sones 5.4 5.4 5.4 5.7 6.0 6.3 6.4 6.7
CFM 443 413 405 351 305
SP-A410 1000 1.74 121 3.0
Sones 4.1 3.8 3.7 3.7 4.3
CFM 557 512 501 439 392 325
SP-A510 1070 3.30 224 4.5
Sones 6.0 5.7 5.6 5.5 5.4 4.7
CFM 757 729 723 700 679 649 613 560 396
SP-A700 1100 3.20 350 5.5
Sones 6.1 6.1 6.1 6.3 6.7 7.1 7.3 7.5 7.7
CFM 752 714 701 653 588 485 320
SP-A710 1080 4.40 285 6.0
Sones 7.4 7.2 7.2 7.0 6.8 6.7 6.7
CFM 812 782 775 741 704 665 625 581
SP-A780 1600 3.30 348 8.5
Sones 10.2 10.2 10.2 9.9 9.5 9.5 9.4 9.4
CFM 955 907 896 841 773 701
SP-A900 950 4.00 285 4.5
Sones 5.2 5.7 5.8 6.1 6.2 6.2
CFM 1125 1059 1043 964 885 796 662
SP-A1050 1095 6.30 420 6.0
Sones 7.2 7.0 6.9 6.8 6.6 6.5 6.5
CFM 1455 1414 1404 1353 1307 1262 1218 1174
SP-A1410 1450 7.40 786 9.5
Sones 11.6 11.6 11.7 11.6 11.5 11.6 11.6 11.6
CFM 1607 1568 1558 1506 1449 1407 1369 1323
SP-A1550 1610 8.60 818 10.0
Sones 12.4 12.1 12.1 12.0 11.9 12.8 14.1 15.9
Outlet connection width is 1 inch - Mounting bracket width is 1½ inch.
For complete dimensional information, see CAPS submittal drawings.
All dimensions are in inches.
A
B
C
D
E
1 HVI sones at 0.1 wg
2 Available with light
5 UL Listed for use above tubs.
6 Available with 277 volt motor.
3 Available with CRD - Ceiling Radiation Damper
4 Available with 50 Hz motors (See CAPS for performance)
2,3,5,6
3,4
3
3
3
3
3
3,4,5
3,5
1
3,4
3,5
3,4,5,6
3,4,5
3,4
3,4
2,3,4,5,6
2,3,5
2,3,5
2,3,5
Standard Decorative Unit
Model
A B C D E
Grille
Grille Wt.
50, 70, 90 13
1
/4 10
5
/8 11
5
/8 6 DIA. 14
7
/8 x 13
1
/4 15
1
/4 sq. 12
110, 125, 190 13
1
/4 10
5
/8 10
1
/2 8 6 14
7
/8 x 13
1
/4 15
1
/4 sq. 17
200, 250, 290, 390 14 11
7
/8 11
1
/4 8 8 14
7
/8 x 13
1
/4 15
1
/4 sq. 24
410, 510 18 14
3
/8 14
1
/2 8 8 19
3
/8 x 16
3
/8 - 31
700 23
5
/8 11
5
/8 11
5
/8 19
1
/2 8 25
1
/8 x 13
1
/2 - 34
710, 780 18 14
3
/8 14
1
/2 10 8 19
3
/8 x 16
3
/8 - 34
900, 1050, 1410, 1550 23
3
/4 14
3
/8 14
1
/2 18
3
/4 8 25 x 16
3
/8 - 56
A
B
C
D
E
®
16